                                                COMMANDER C
Commander C specifications
       Ambient Operating Temperature
Cooling method Humidity
Storage Temperature
Altitude Vibration Mechanical Shock Enclosure Rating
Electromagnetic Capability RoHS
Voltage
Phase Maximum Supply Imbalance Input Frequency Input Displacement Power Factor
Switching Frequency
Output Frequency Range Frequency Accuracy Frequency Resolution Analog Input Resolution Braking
DC Bus Undervoltage Trip
DC Bus Overvoltage Trip
Drive Overload Trip Instantaneous Overcurrent Trip Phase Loss Trip Over-temperature Trip Short Circuit Trip Ground Fault Trip Motor Thermal Trip
UL, cUL CE
EU
RCM ISO
TÜV
Environment
Size 1 - 4: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. Size 5 - 9: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. Size 1- 4: Operation to 60°C (140°F) with de-rating
Size 5 - 9: Operation to 55°C (131°F) with de-rating
Forced convection
95 % non-condensing at 40 °C (104 °F)
Size 1 - 4: -40°C to 60°C (-40°F to 140°F) — 24 months Max. Size 5 - 9: -40°C to 55°C (-40°F to 131°F) — 24 months Max.
De-rate the continuous output current by 1% for every 100 m (328 ft) above 1000 m (3,280 ft) to a maximum of 3000 m (9,840 ft) Tested in accordance with IEC 60068-2-64 and IEC 60068-2-6
Tested in accordance with IEC 60068-2-27 and IEC 60068-2-29
IP20, NEMA 1 conduit kits available
IEC/ EN 61800-3 Immunity and Emissions
EN 61000-6-2: Immunity for industrial environments EN 61000-6-4: Emissions for industrial environments EN 61000-3-2: Harmonic current emissions
An EMC data sheet is available on request
Complies with the Restriction of Hazardous Substances Directive (2011/65/EU)
AC Supply Requirements
100 V models: 100 to 120 Vac ±10% 200 V models: 200 to 240 Vac ±10% 400 V models: 380 to 480 Vac ±10%
1Ø and 3Ø (Model dependent)
2% negative phase sequence, 3% voltage imbalance between phases 45to66Hz
0.97
Control
Size1-4:0.667,1,2,3,4,6,812&16kHz Size 5 - 9: 2, 3, 4, 6, 8 12 & 16 kHz
0to550Hz
±0.02% of full scale
0.01 Hz
Voltage mode: 11 bits (unipolar) Current mode: 11 bits
Dynamic braking transistor included, requires external resistor
                                              Protection
  100 V models: 175 Vdc 200 V models: 175 Vdc 400 V models: 330 Vdc
Frame sizes 1 - 4:
100 V models: 510 Vdc 200 V models: 510 Vdc 400V models: 870 Vdc Frame size 5 - 9:
200V models: 415 Vdc 400 V models: 830 Vdc
    Programmable: Default settings: 180% for 3s, 150% for 60s 220% of rated motor current
DC bus ripple threshold exceeded
Drive heatsink temperature exceeds 95°C (203°F) Protects against output phase-to-phase fault
Protects against output phase-to-ground fault
Electronically protects the motor from overheating due to loading conditions
Approval & Listings
UL file NMMS/8: E171230 CE approval
These products comply with the Restriction of Hazardous Substances Directive (2011/65/EU), the Low Voltage Directive (2014/35/ EU) and the Electromagnetic Compatibility Directive, (2014/30/EU).
RCM Registered supplier No. 12003815281
Manufacturing facilities comply with ISO 9001:2015 and ISO 14001
C300 models only: The Safe Torque Off (STO) function may be used as a safety component of a machine.
Type examination certificates by TuV Rheinland: Frame sizes 1 - 4: No. 01/205/5383.03/18 Frame sizes 5 - 9: No. 01/205/5387.02/18
                           Functional safety parameters:
EN ISO 13849-1 - Cat 4, PLe EN61800-5-2/EN62061/IEC 61508 - SIL 3
UL functional safety approval: FSPC E171230