  TWIN & EARTH CABLE 6491X SINGLES CABLE
 6491X / H07V-R / H07V-U / BS EN 50525-2-31 Cable
Application
6491X Cable H07V-R/H07V-U is suitable for power and lighting circuits and building wiring. The cable is intended for use in semi-flush exposed conduits and embedded conduits as well as in closed installation ducts, and is ideal for the internal wiring of appliances.
Construction
• Conductor - H07V-R: Class 2 stranded copper conductor to BS EN 60228 (previously BS 6360) H07V-U: Class 1 solid copper conductor to BS EN 60228 (previously BS 6360)
• Insulation - PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
Characteristics
• Voltage Rating (Uo/U) - 450/750V
• Temperature Rating - -15°C to +70°C
• Minimum Bending Radius - Up to 10mm2: 3 x overall diameter / 10mm2 to
25mm2: 4 x overall diameter / Above 25mm2: 5 x overall diameter
• Insulation Colour - Red Black Blue Yellow White Green/Yellow Grey Brown Cable Standards
• BS EN 50525-2-31 (previously BS 6004) BASEC approved, BS EN/IEC 60332-1-2
 Nominal Cross Sec- Part Number tional Area (mm2)
A2X*0015 1.5
A2X*0025 2.5
Nominal Thickness of Insulation (mm)
0.7
0.8
0.8
0.8
1
1
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2
2.2
2.4
2.6
2.8
2.8
Nominal Overall Diameter (mm)
2.9
3.6
4.1
4.7
5.9
6.8
8.4
9.4
11
12.7
14.7
16.2
18
20
23
25.2
28.4
31.8
38.1
Nominal Weight (kg/km)
22
32
50
71
110
164
256
346
473
674
913
1150
1416
1749
2317
3049
3657
4700
5890
   A2X*0040
A2X*0060
4
6
  A2X*010 10
A2X*016 16
A2X*025 25
A2X*035 35
A2X*050 50
A2X*070 70
A2X*095 95
A2X*120 120
A2X*150 150
A2X*185 185
A2X*240 240
A2X*300 300
A2X*400 400
A2X*500 500
A2X*630 630
               *Eland Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A2XRD0040 = 4mm2 Red
Colour Codes
Colour Black Blue Grey Green/Yellow Red Yellow Brown
White
 Code BK BL GR GY RD YW BR WH
  BS 6004 624-Y Twin and Earth PVC Cable
Application
Domestic wiring cable. Can be installed in fixed installations in dry or damp premises clipped to surface, on trays or in free air where the risk of mechanical damage would not be an issue. Suitable for laying in conduit or trunking where mechanical protection is required.
Construction
• Conductor - Copper conductor according to BS EN 60228 (previously BS 6360) / 1mm2 to 2.5mm2: Class 1 solid conductor / 4mm2 to 16mm2: Class 2 stranded conductor
• Circuit Protection Conductor (Earth) - 1mm2 to 2.5mm2: Class 1 solid copper conductor / 4mm2 to 16mm2: Class 2 stranded copper conductor
   • Insulation - PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
• Sheath - PVC (Polyvinyl Chloride) Type 6 according to BS 7655 Characteristics
• Voltage Rating (Uo/U) - 300/500V
• Temperature Rating - -5°C to +70°C / Short Circuit : +160°C
• Minimum Bending Radius - Fixed: 6 x overall diameter
• Core Identification - Brown Blue
• Sheath Colour - Grey
Cable Standards
• BS 6004 Table 4
No. of Cores
2
2
2
2
2
2
2
3
3
Nominal Cross Sectional Area (mm2)
1
1.5
2.5
4
6
10
16
1
1.5
Conductor Class
Cross Sec- tional Area of Circuit Protective Conductor (mm2)
Nominal Thickness of Insulation (mm)
0.6
0.7
0.8
0.8
0.8
1
Nominal Thick- ness of Sheath (mm)
0.9
0.9
1
1
1.1
1.2
1.3
0.9
0.9
Nominal Overall Dimensions (mm)
4.35x7.95
4.85x8.9
5.65x10.65
6.3x11.95
7.1x13.7
8.7x17.25
9.85x20
4.35x9.8
4.85x11.2
 11
11
1 1.5
2 1.5
2 2.5
2 4*
      2 6* 1
1 1 0.6
11 0.7
   FIRE RESISTANT CABLE
 Standard Fire Resistant Cable BS7629-1 LPCB BASEC Approved
Application
Hard Skin Standard Fire Resistant Cables for use primarily in fire detection, fire alarm, voice alarm, and emergency lighting circuits. These cables are designed to continue to operate for a period of time in a fire situation. ‘Standard’ fire resistance is recommended for general use.
Construction
• Conductor - 1.5mm2 - 2.5mm2: Class 1 solid conductor according to BS EN 60228 / 4mm2: Class 2 stranded conductor according to BS EN 60228
• Insulation - High performance fire resistant silicone rubber
• Overall Screen - AL/PET (Aluminium/Polyester Tape)
• Circuit Protective Conductor - Tinned copper
• Outer Sheath - LSZH (Low Smoke Zero Halogen) Thermoplastic Characteristics
• Voltage Rating - 300/500V
• Operating Temperature - -40°C to +90°C
• Minimum Bending Radius - 6 x overall diameter
• Core Identification - 2 cores: Blue Brown + Bare Earth / 3 cores: Brown
Black Grey + Bare Earth / 4 cores: Blue Brown Black Grey + Bare Earth
• Outer Sheath Colour - Red White